EasyManua.ls Logo

YASKAWA T1000V - Page 274

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.9 Troubleshooting without Fault Display
274 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Overvoltage Occurs When Running at a Constant Speed
Motor Stalls During Acceleration or With Large Loads
Motor Will Not Accelerate or the Acceleration Time is Too Long
Cause Possible Solutions
Excessive load inertia in Open Loop Vector Control.
Loads with a lot of inertia (fans, etc.) can trigger an overvoltage fault when operating in
Open Loop Vector Control.
Switch to the V/f motor control method.
Adjust the values set for the speed feedback detection control time constant (n2-02 and
n2-03).
Cause Possible Solutions
Load is too heavy.
Take the following steps to resolve the problem:
Reduce the load.
Increase the acceleration time.
Increase motor capacity.
Although the drive has a Stall Prevention function and a Torque Compensation Limit
function, accelerating too quickly or trying to drive an excessively large load can exceed
the capabilities of the motor.
Cause Possible Solutions
Frequency reference is too low.
Check the maximum output frequency (E1-04).
Increase E1-04 if it is set too low.
Check U1-01 for proper frequency reference.
Check if a frequency reference signal switch has been set to one of the multi-function input terminals.
Check for low gain level set to terminals A1 or A2 (H3-03 or H3-11).
Load is too heavy.
Reduce the load so that the output current remains within the motor-rated current.
Check if the mechanical brake is fully releasing as it should.
The torque limit function is
operating in Open Loop Vector
Control.
Check the torque limit setting. It may be too low. (L7-01 through L7-04).
Reset the torque limit to its default value (200%).
Acceleration time has been set too
long.
Check if the acceleration time parameters have been set too long (C1-01, C1-03, C1-05, C1-07).
Motor characteristics and drive
parameter settings are incompatible
with one another in V/f Control.
Set the correct V/f pattern so that it matches the characteristics of the motor being used.
Check V/f Pattern.
The right combination of motor
characteristics have not been set in
Open Loop Vector Control.
Execute Rotational Auto-Tuning.
Incorrect frequency reference
setting.
Check the multi-function analog input settings.
Check if multi-function analog input terminal A1 or A2 is set for frequency gain (H3-02 or H3-10 = “1”). If
so, the frequency reference will be 0 if there is no voltage (current) input provided.
Ensure H3-02 and H3-10 are set to the proper values.
Ensure the analog input value is set to the right value (U1-13 or U1-14).
The Stall Prevention level during
acceleration and deceleration set
too low.
Check the Stall Prevention level during acceleration (L3-02).
If L3-02 is set too low, acceleration will take a fair amount of time.
Increase L3-02.
The Stall Prevention level during
run has been set too low.
Check the Stall Prevention level during run (L3-06).
If L3-06 is set too low, speed will drop as the drive outputs torque.
Increase the setting value.
Although the drive is operating in
Open Loop Vector motor control
method, Auto-Tuning has not been
performed.
Perform Auto-Tuning.
Calculate motor data and reset motor parameters.
Switch to the V/f motor control method (A1-02 = “0”).
Drive reached the limitations of the
V/f motor control method.
The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance.
Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds.
Consider switching to Open Loop Vector Control.

Table of Contents

Related product manuals