B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 349
L8-07
Output Phase Loss
Protection Selection
Selects the output phase loss detection.
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Output phase loss is detected when operating with less than
5% of the drive rated current. Detection can mistakenly
occur if the motor is too small relative to the drive capacity
rating (this parameter should be disabled in such cases).
0 to 2 1 A A A 4B3 201
L8-09
Output Ground Fault
Detection Selection
Selects the output ground fault detection.
0: Disabled
1: Enabled
0, 1
<11> AAA 4B5 202
L8-10
Heatsink Cooling Fan
Operation Selection
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only when the
drive is running and for L8-11 seconds after stop.
1: Fan always on - Cooling fan operates whenever the drive
is powered up.
0, 1 0 A A A 4B6 202
L8-11
Heatsink Cooling Fan Off-
Delay Time
This parameter sets the delay time for the cooling fan to
shut off after the run command is removed when L8-10 = 0.
0 to 300 60 s A A A 4B7 202
L8-12
Ambient Temperature
Setting
Used to input the ambient temperature. This value adjusts
the drives oL2 detection level.
-10 to 50 40 °C A A A 4B8 202
L8-15
oL2 Characteristics
Selection at Low Speed
Sets the oL2 characteristics at output frequencies below 6
Hz.
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0
Hz.
0, 1 1 AAA 4BB 202
L8-18
Software Current Limit
Selection
Selects the software current limit function. Typically no
adjustment is required.
0: Disabled
1: Enabled
0, 1
1
<1>
AA− 4BE 203
L8-29
Current Unbalance
Detection (LF2)
Selects the detection of unbalanced output currents caused
by faulty devices in the output circuit.
0: Disabled
1: Enabled
0 to 1 1 −−A4DF203
L8-35
<18>
Installation Method
Selection
Selects the installation type:
0: Heatsink-Cooled Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
0 to 2
<11> ΑΑA4EC203
L8-38
Carrier Frequency
Reduction Selection
Provides protection to the IGBTs by reducing the carrier
frequency at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
0 to 2
<11> AAA 4EF 204
L8-40
Carrier Frequency
Reduction Off-Delay Time
Sets the time for that the drive continues running with
reduced carrier frequency after the carrier reduction
condition has gone (see also L8-38).
A setting of 0.00 s disables the carrier frequency reduction
time.
0.00 to
2.00
0.50 A A A 4F1 204
L8-41
High Current Alarm
Selection
Configures an alarm when the output current exceeds
150% of the drive rated current.
0: Alarm disabled.
1: Alarm enabled.
0, 1 0 A A A 4F2 204
L8-46 AVR Function Selection
Allows the drive to automatically adjust the drive output
voltage.
0: Disabled
1: Enabled
0, 1 1 A A A 4FA 204
L8-51
<38>
STo Level
Sets the STo detection level as a percentage of the motor
rated current. If set to zero, then the drive will
automatically calculate an appropriate detection level.
0.0 to
150.0%
0.0% −−A471205