B.3 Parameter Table
362 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
U4-16
Motor Overload Estimate
(oL1)
100% = oL1 detection level
100% = oL1
detection level
0.1% A A A 7D8
U4-18
Frequency Reference
Source Selection
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Operator (d1-01)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 17 = Multi-step speed (d1-02 to 8, 17)
3-01 = MEMOBUS/Modbus comm.
4-01 = Option
5-01 = Pulse Input
6-01 = Not used
7-01 = Not used
––AAA7DA
U4-19
Frequency Reference from
MEMOBUS/Modbus
Comm.
Displays the frequency reference provided by
MEMOBUS/Modbus (decimal).
––AAA7DB
U4-20
Option Frequency
Reference
Displays the frequency reference input by an option card
(decimal).
––AAA7DD
U4-21
Run Command Source
Selection
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Operator
1 = External terminals
2 = Not used
3 = MEMOBUS/Modbus communications
4 = Option
5 = Not used
6 = Not used
7 = Not used
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG
mode.
02: Run command was left on when switching from
LOCAL to REMOTE operation.
03: Waiting for the soft charge bypass contactor after the
power is switched on (Uv or Uv1 flashes after 10
seconds).
04: Waiting for “Run Command Prohibited” time period
to end.
05: Fast-stop (digital input (H1- = 15), operator)
06: b1-17 (run command given at power-up).
07: During Baseblock while coast to stop with timer
08: Frequency reference is below minimal reference
during Baseblock
09: Waiting for Enter command
10: Run command enabled while copying parameter
settings
––AAA7DD
U4-22
MEMOBUS/Modbus
Communications Reference
Displays the drive control data set by MEMOBUS/
Modbus communications register No. 0001H as a 4 digit
hexadecimal number.
——AAA7DE
U4-23
Communication Option
Card Reference
Displays drive control data set by an option card as a 4
digit hexadecimal number.
——AAA7DF
No. Name Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/f
OL
V
P
M