C.10 MEMOBUS/Modbus Data Table
398 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
003DH
Communications Error Contents
<3>
bit 0 CRC Error
bit 1 Data Length Error
bit 2 Reserved
bit 3 Parity Error
bit 4 Overrun Error
bit 5 Framing Error
bit 6 Timeout
bit 7 to bit F Reserved
003EH
Output Frequency
r/min <4>
003FH 0.01% units
0040H to 004AH Used for various monitors U1-. Refer to U: Operation Status Monitors on page 358 for parameter details.
004BH
Drive status (U1-12)
bit 0 During Run
bit 1 During Zero Speed
bit 2 During Reverse Run
bit 3 During Fault Reset Signal Input
bit 4 During Speed Agree
bit 5 Drive Ready
bit 6 Alarm
bit 7 Fault
bit 8 During Operation Error (oPE)
bit 9 During Momentary Power Loss
bit A Motor 2 selected
bit B Reserved
bit E ComRef status, NetRef status
bit F ComCtrl status, NetCtrl status
004CH to 007E
Used for various monitors U1-, U4-, U5- and U6-. Refer to U: Operation Status Monitors on page 358
for parameter details.
007FH Alarm Code, Refer to Alarm Register Contents on page 403 for alarm codes.
0080H to 0097H
Used for monitors U2-, U3-. Refer to U: Operation Status Monitors on page 358 for parameter details and Refer
to Fault Trace Contents on page 402 for register value descriptions.
0098H High Word of Accumulated Operation Time Monitor (U4-01)
0099H Low Word of Accumulated Operation Time Monitor (U4-01)
009AH High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH Low Word of Cooling Fan Operation Time Monitor (U4-03)
00ABH Drive Rated Current <2>
00ACH
Motor Speed (Open Loop
Vector only)
r/min units <4>
00ADH 0.01% units
00B0H Option Code
Register contains ASCII code of 3rd and 4th digit of the option card type number. Example:
Register value is 5343H for “P3” if a SI-P3 option card is installed.
00B5H
Frequency Reference After
Soft-starter
r/min units <4>
00B6H 0.01% units
00B7H
Frequency Reference
r/min <4>
00B8H 0.01% units
00BFH oPE Error Number
Register No. Contents