D.3 UL Standards
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 417
Use UL compliant fuses listed in the following table when wiring the main circuit. Branch circuit protection shall be
provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Exceptional models are A6T6 with 2V0002, A6T15 with 2V0004 or 4V0004, A6T20 with 4V0005, and A6T25 with 4V0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Table D.5 Recommended Input Fuse Selection
■ Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class
2 (UL regulations) power supply for the control circuit terminal.
Table D.6 Control Circuit Terminal Power Supply
Drive Model CIMR-T
Non-Time Delay Class-T
Fuse Type
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
Fuse Ampere Rating
(A)
Fuse Type
(Manufacturer: Bussmann)
500 Vac, 200 kAIR
Fuse Ampere Rating
(A)
Single-Phase 200 V Class
BV0001 A6T6 6 FWH-25A14F 25
BV0002 A6T10 10 FWH-25A14F 25
BV0003 A6T20 20 FWH-60B 60
BV0006 A6T40 40 FWH-80B 80
BV0010 A6T40 40 FWH-100B 100
BV0012 A6T50 50 FWH-125B 125
Three-Phase 200 V Class
2V0001 A6T3 3 FWH-25A14F 25
2V0002 A6T6 6 FWH-25A14F 25
2V0004 A6T15 15 FWH-25A14F 25
2V0006 A6T20 20 FWH-25A14F 25
2V0010 A6T25 25 FWH-70B 70
2V0012 A6T30 30 FWH-70B 70
2V0020 A6T40 40 FWH-90B 90
2V0030
Not Available
FWH-100B 100
2V0040 FWH-200B 200
2V0056 FWH-200B 200
2V0069 FWH-200B 200
Three-Phase 400 V Class
4V0001 A6T3 3 FWH-40B 40
4V0002 A6T6 6 FWH-40B 40
4V0004 A6T15 15 FWH-50B 50
4V0005 A6T20 20 FWH-70B 70
4V0007 A6T25 25 FWH-70B 70
4V0009 A6T25 25 FWH-90B 90
4V0011 A6T30 30 FWH-90B 90
4V0018
Not Available
FWH-80B 80
4V0023 FWH-100B 100
4V0031 FWH-125B 125
4V0038 FWH-200B 200
Input / Output Terminal Signal Power Supply Specifications
Open Collector Outputs P1, P2, PC Requires class 2 power supply.
Digital Inputs / Outputs
S1, S2, S3, S4, S5, S6, SC,
HC, H1, RP, MP
Use the internal LVLC power supply of the drive. Use class 2 for external
power supply.
Analog Inputs / Outputs +V, A1, A2, AC, AM
Use the internal LVLC power supply of the drive. Use class 2 for external
power supply.