<8.  OPERATION VIA HART CONFIGURATION TOOL (HART 5)>
8-1
IM 01E30D01-01EN
8. 
OPERATION VIA HART CONFIGURATION TOOL (HART 5)
ThisChapterdescribesthedevice(AXR)operation
proceduresusingaHARTcongurationTool(such
as FieldMate).
NOTE
For more details regarding the operations for 
theHARTcongurationtool,readtheHART
congurationtooloperationsmanual.
Note:  HART is a registered trademark of the 
FieldComm Group.
8.1  HART Protocol Revision
For the models with the output signal code “-J”, 
HART protocol revision 5 or 7 is selectable. The 
protocolrevisionissetasspeciedintheorder.
Howtoconrmprotocolrevisionisshownbelow.
Therearetwowaystoconrmtheprotocolrevision
set to the transmitter.
(1)Conrmationbythenameplate
  The HART protocol revision at the time of 
shipment is shown by the last number at the 
serial number column of the name plate.
F0801.ai
XXX…XX   
5: HART 5
7: HART 7
(2) ConrmationbyusingHARTcongurationtool
  Read Subsection 8.8.5.
IMPORTANT
Protocol revision supported by HART 
congurationtoolmustbethesameorhigher
than that of the device. 
Protcol revision 
supported by HART 
congurationtool
5 7
Protocol revision of 
the device
5
 
7 ×
   : Communication OK
×: Communication NG
NOTE
In this User’s Manual, HART protocol revision 
5 and 7 are described as HART 5 and HART 7 
respectively.
NOTE
When the output signal code of the device is “-J”, 
HART protocol revision can be changed.  Read 
Subsection 8.8.5 about the procedure of the 
revision change of HART 5 and HART 7.
8.2  Device Description (DD) on 
aHARTCongurationTool
and AXR Device Revision
8.2.1  DD Revision and Device Revision
BeforeusingtheHARTCongurationTool(such
asFieldMate),conrmthattheDD(Device
Description)oftheAXRisinstalledinthe
CongurationTool.
• AXR:HART5
• Devicetype:0x57
• DeviceRevision:2
• DDRevision:2
TheDDrevisionsforAXRandCongurationTool’s
canconrminaccordancewiththefollowingsteps.
If the correct DD is not installed in the HART 
CongurationTool,downloadthemfromtheHART
ofcialsite,otherwise,contacttherespective
vendorsoftheCongurationToolforitsupgrade
information.
1. ConrmationofthedevicerevisionforAXR
(1) ConnecttheCongurationTooltotheAXR.
The device revision can be checked as 
follows.
DD DeviceSetup→Review→Review4
→Flddevrev
2. Conrmationofthedevicerevisionforthe
HARTCongurationTool
(1) TurnonthepoweroftheCongurationTool
under the standalone condition.