<6.  PARAMETER DESCRIPTION>
6-2
IM 01E30D01-01EN
6.3  Parameter List Overview
(1)  Item A (Menu A): Display items
MenuAcontainstheinstantaneousowrate,totalizationvalues,andotheritemsrelevanttodisplay.
Item 
Name 
R/W
Data range 
Units 
Position 
of decimal 
point 
Default value 
(*): Indicated item 
Description
Display unit
(BRAIN) 
Display unit
/BRAIN
A00  Display 
(DISPLAY) 
A10  FR 
(FLOW RATE (%)) 
R  -103.1 to 103.1  %  1  For Display Mode only 
A20  FR 
(FLOW RATE) 
R  -999999 to 999999 
B21/B22 
(C40/C41) 
0 to 3  For Display Mode only 
A21  FR 
(FLW RATE (mA)) 
R  3.800 to 20.500  mA  3  For Display Mode only 
A30  FTL 
(TOTAL) 
R  0 to 99999999  B30 
(D10) 
0 to 7  For Display Mode only 
A31  RTL 
(REV TOTAL) 
R  0 to 99999999  B30 
(D10) 
0 to 7  For Display Mode only 
A32  DTL 
(DIF TOTAL) 
R  -99999999 
to 99999999 
B30 
(D10) 
0 to 7  For Display Mode only 
A60  — 
(SELF CHECK) 
R  Good 
Error 
Read Section 6.5 “Alarm 
Functions”. 
(2)  Item B (Menu B): Easy Setup items
Those parameters with a high frequency of use have been grouped together in Menu B. All basic functions can 
be controlled using only the parameters from this block.
Item 
Name 
R/W
Data range 
Units 
Position 
of decimal 
point 
Default value 
(*): Indicated item 
Description
Display unit
(BRAIN) 
Display unit
/BRAIN
B00  Easy Setup 
(EASY SETUP) 
B10  Language 
(LANGUAGE) 
W  English 
Japanese 
French 
German 
Italian 
Spanish 
English  Selects the language used for 
the display unit. Linked with 
H30. 
B20  Flow Damping 
(FLOW DAMPING) 
W  1.0 to 200.0  s  1  5.0 s  Sets damping time. Linked with 
C11. 
B21  Base Flow Unit 
(FLOW UNIT) 
W  Ml(Megaliter) 
m
3
 
kl (Kiloliter) 
l (Liter) 
cm
3
 
m 
t 
kg 
g 
kcf 
cf 
mcf 
Mgal (US) 
kgal (US) 
gal (US) 
mgal (US) 
kbbl (US Oil) 
bbl (US Oil) 
mbbl (US Oil) 
ubbl (US Oil) 
kbbl (US Beer) 
bbl (US Beer) 
mbbl (US Beer) 
ubbl (US Beer) 
ft 
klb (US) 
lb (US) 
m (*)  Selectsowunitsfortheow
rate span. Linked with C40.