<6. PARAMETER DESCRIPTION>
6-16
IM 01E30D01-01EN
6.4 Parameter Description
IMPORTANT
One output can be selected from pulse, alarm, or
status through the parameter setting.
(1) Menu B: Easy Setup items
Those parameters with a high frequency of use
have been grouped together in Easy Setup. All
basic functions can be controlled using only the
parameters from this block. Parameters from
Menu B share identical names with those from
othermenus;however,modicationofonesuch
parameter will result in the other being automatically
modied.
[B10: Language] Selection of language used for
the display unit
→ This setting is linked with that of parameter H30.
One of the following languages can be selected for
the display unit.
Data Range
Setting item Description
English All parameters, alarm messages, etc. displayed
in English.
Japanese All parameters, alarm messages, etc. displayed
in Japanese katakana.
French All parameters, alarm messages, etc. displayed
in French.
German All parameters, alarm messages, etc. displayed
in German.
Italian All parameters, alarm messages, etc. displayed
in Italian.
Spanish All parameters, alarm messages, etc. displayed
in Spanish.
[B20: Flow Damping] Setting of the damping time
constant
→ This setting is linked with that of parameter C11.
Thedampingtimeconstantshouldbemodiedto
suppressanoutputuctuationortochangethe
response time. This time constant has an effect
onanalogoutputandontheowratedisplay(i.e.,
actualinstantaneousowrate,%,currentvalue),
and in addition, it also affects pulse output and
totalization. However, when “No Damping” has
been set for J25:T/PDampSelect, there will be no
effect on pulse output or totalization.
*: Time constant: The time required for the output to reach
63.2% from 0%.
NOTE
When the damping time is short, the output
uctuates.Setthetimeto5secondsormorefor
control loop.
[B21: Base Flow Unit] Selectionofowunitsfor
theowratespan
→ This setting is linked with that of parameter C40.
Thisparameterselectstheowunitsfortheow
ratespan.(Incaseofmassow,thesettingof
density is also required. Read C46: Mass Flow
Density for more details.)
[B22: Base Time Unit] Selection of time units for
theowratespan
→ This setting is linked with that of parameter C41.
Thisparameterselectsthetimeunitsfortheow
rate span; however, if “m” has been selected for
theowrateunits,“/s”isautomaticallysetforthis
parameter.
[B23: Flow Span]Settingoftheowratespan
→ThissettingislinkedwiththatofparameterC42.
Thespancanbesetfortheforwardowrateinthe
range 0 to 32,000 (although this does not include 0).
The units set using B21/C40:BaseFlowUnit and
B22/C41:BaseTimeUnit will be displayed at this
time.