<9.  OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-3
IM 01E30D01-01EN
NOTE
Before updating any setting, remember to always 
check the parameter content you want to change 
as described in Chapter 6.
NOTE
IncaseofHARTConguration,theparameters
are displayed in English only.
Even if the language with the exception of 
English is selected at “Language” setting display, 
the parameters are displayed in English upon 
HARTCongurationTool.
9.4  Basic Setup
 ConrmationandChageofTagand
Device Information
The tag number and device information can be 
checked as follows:
• Thelocationforthetagnumberanddevice
information
Tag [Root Menu]→DetailedSetup
→Basicsetup→Tag
Long tag [Root Menu]→DetailedSetup
→Basicsetup→Long tag
Descriptor [Root Menu]→DetailedSetup
→Deviceinfo→Fielddeviceinformation
→Descriptor
Message [Root Menu]→DetailedSetup
→Deviceinformation
→Fielddeviceinformation→Message
Date [Root Menu]→DetailedSetup
→Deviceinfo→Fielddeviceinformation
→Date
When changing the tag number or device 
information, enter the information directly within the 
following limitations.
Item Limitations
Tag Up to 8 characters or numbers*
1
Long tag
Up to 32 characters or numbers*
2
Descriptor Up to 16 characters or numbers*
1
Message Up to 32 characters or numbers*
1
Date mm/dd/yyyy (DD)
yyyy/mm/dd (DTM)
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
9.5 ParametersConguration
TheparameterstructureoftheHARTconguration
tool is hierarchical.
Read Section 9.9, Menu Tree Example for the 
corresponding parameters. The menu tree shows 
a cross-reference of the parameters for HART and 
BRAIN.
Read Chapter 6 for the functions of parameters.
NotethatsomedisplayparametersofAXRare
differentfromthoseofHARTcongurationtools.
9.6  Data Renewing
TherearetwomethodstoloadtheAXRdata
from/toHARTCongurationTool---periodicdata
renewing and discretionary data renewing. Read 
Section 9.9 menu tree for each corresponding 
parameter.
(1)  Periodic Data Renewing
  The data is updated 0.5 to 2 second cycles. The 
parameter of this type is marked as “D” in “Data 
Renewing” of Section 9.9 menu tree.
(2)  Discretionary Data Renewing
 Thedatacanbeloadedfrom/totheAXRwhen
thedatasaveisnishedtotheConguration
Tool. The parameter of this type is marked as 
“S” in “Data Renewing” of Section 9.9 menu 
tree.
NOTE
TheAXRisnotabletosetparametersviaits
display unit during a communication of the HART 
CongurationTool.