Common mode filter (+E208, see Requirements tables (page 75))6
du/dt filter (optional, see Filters (page 279))7
EMC filter (+E210)8
The drive module frame must be connected to the cabinet frame. See section Alternatives for
grounding the drive module (page 68).
9
External brake resistor10
Preparing the cable ends Symmetrical shielded cables
1. Peel off 3…5 cm (1¼ 2 in) of the outer insulation of the cables at the cable
entries with the conductive sleeves for the 360° high-frequency grounding.
2. Prepare the ends of the cables.
PE
PE
WARNING!
Apply grease to stripped aluminum conductors before attaching them to
non-coated aluminum cable lugs. Obey the grease manufacturer’s
instructions. Aluminum-aluminum contact can cause oxidation in the
contact surfaces.
106 Electrical installation