Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Reverse15.07 RO4 source
1 s15.08 RO4 ON delay
1 s15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Digital output15.22 DO1 configuration
Reverse15.23 DO1 source
1 s15.24 DO1 ON delay
1 s15.25 DO1 OFF delay
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate
the motor speed 0…1500 rpm with a frequency range of 0…10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
1000 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
■ Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Technical data
Into an option slot on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
270 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O)