Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CAIO-01.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of 15.02 is CAIO-01
set the value of parameter 15.01 to CAIO-01.
You can now see the parameters of the extension module in group 15 I/O extension
module.
3. Set the parameters of analog inputs AI3, AI4, AI5 or analog outputs AO3 or AO4
to applicable values, see the firmware manual.
Example: To connect supervision 1 to AI3 of the extension module:
Select the mode of the supervision function (32.05 Supervision function 1).
Set limits for the supervision function (32.09 Supervision 1 low and 32.10
Supervision 1 high).
Select the supervision action (32.06 Supervision 1 action).
Connect 32.07 Supervision 1 signal to 15.52 AI3 scaled value.
Diagnostics
LEDs
The adapter module has one diagnostic LED.
DescriptionColor
The adapter module is powered up.Green
There is no communication with the drive control unit or the adapter module has
detected an error.
Red
Technical data
Into slot 2 of drive control unitInstallation
IP20 / UL 1 TypeDegree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Analog inputs (80..82, 83..85, 86..88)
1.5 mm
2
Maximum wire size
-11 V +11 VInput voltage ( AI+ and AI-)
-22 mA +22 mAInput current ( AI+ and AI-)
>200 kohm (voltage mode), 100 ohm (current mode)Input resistance
Optional cable shield connections
Analog outputs (90..92, 93..95)
252 CAIO-01 bipolar analog I/O adapter module