Installation positions other than vertical
You can install the drive module on its back. Make sure that the hot cooling air which
flows upwards from the module does not cause danger.
For other installation positions, contact ABB.
Free space requirements
Free space around the drive module is needed to make sure that sufficient cooling air
flows through the module and the module cools correctly.
Free space at the top of the drive module
The free space requirement at the top of the module is shown below.
Air outlet in the upper part of the cabinet doorAir outlet on the cabinet roof
290 mm
(11.42 in)
1
2
1
270 mm
(10.63 in)
1
2
1
Air inlet1
Air outlet2
Free space around the drive module
Bookshelf installation: 10 mm (0.39 in) free space around the drive module is required
from the cabinet back panel and front door. No free space for cooling is required on
the left- and right-hand sides of the module.
The module can be installed in a cabinet with the following dimensions:
width 400 mm (15.75 in)
depth 600 mm (23.62 in)
height 2000 mm (78.74 in).
Free space below the drive module
Standard drive module: No free space for cooling is required at the bottom of the
drive module.
58 Guidelines for planning the mechanical installation