Planning the layout
■ Layout example, door closed
This diagram shows a cabinet layout example with the input power cable entry from
top and the motor cable entry from bottom.
Air inlet for the drive module1a
Air inlet for the other equipment. An extra fan is
not necessary if an extra air baffle is used on the
cabinet roof, see Layout example, door open
(standard drive module configuration) (page 53).
1b
Air inlet for circuit boards and DC and output
busbars
1c
Air outlet with an extra exhaust fan for the drive
module
2a
Air outlet for the other equipment2b
Air outlet for the drive module and other equip-
ment on the cabinet roof. An exhaust fan if
needed. ABB recommends this alternative instead
of 2a.
2c
Drive control panel with DPMP-03 mounting
platform. The control panel is connected to the
drive module control unit inside the cabinet.
3
Contactor control switch and emergency stop
switch (connected to the contactor control circuit
inside the cabinet)
4
Operating handle of the disconnector5
Rubber grommets for degree of protection6
Roof air flow viewed from top7
Note: The sizes of the air inlet and outlet gratings are
critical for the cooling of the drive module. For losses
and cooling data requirements, see section Losses,
cooling data and noise (page 187).
52 Guidelines for planning the mechanical installation