kA
1)
ABB molded case circuit breaker (Tmax)Frame
size
ACS580-04-…
Product ID (Type)
U
n
= 400 V
301SDA054412R1R10505A-4
(T5H 630 PR221DS-LS/I In=630 3p F F)
301SDA069428R1R10585A-4
(T6V 800 PR221DS-LS/I In=800 3p F F)
301SDA069428R1R10650A-4
(T6V 800 PR221DS-LS/I In=800 3p F F)
501SDA062770R1R11725A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
501SDA062770R1R11820A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
501SDA062770R1R11880A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
1)
Maximum permitted rated conditional short-circuit current (IEC 61800-5-1) of the electrical power network.
kA
1)
ABB molded case circuit breaker (Tmax)Frame
size
ACS580-04-…
Product ID (Type)
U
n
= 480 V
301SDA054412R1R10505A-4
(T5H 630 PR221DS-LS/I In=630 3p F F)
301SDA054412R1R10585A-4
(T5H 630 PR221DS-LS/I In=630 3p F F)
501SDA062770R1R10650A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
501SDA062770R1R11725A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
501SDA062770R1R11820A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
501SDA062770R1R11880A-4
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
1)
Maximum permitted rated conditional short-circuit current (IEC 61800-5-1) of the electrical power network.
Dimensions, weights and free space requirements
Standard drive module configuration (IP00) and option +B051 (IP20 shrouds)
Weight*DepthWidthHeightFrame size
kgmmmmmm
1615293501462R10
1995293501662R11
Technical data 185