EasyManua.ls Logo

ABB ACS580-04 - Cable Types and Lengths; Grounding of Protective Shields

ABB ACS580-04
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In case a manually operated activation switch is used, the switch must be of a
type that can be locked out to the open position.
The contacts of the switch or relay must open/close within 200 ms of each other.
A CPTC thermistor protection module or an FSPS safety functions module can
also be used. For more information, see the module documentation.
Cable types and lengths
ABB recommends double-shielded twisted-pair cable.
Maximum cable lengths:
300 m (1000 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes a
dangerous fault. Therefore, it is recommended to use a safety relay (including wiring
diagnostics) or a wiring method (shield grounding, channel separation) which reduces
or eliminates the risk caused by the short-circuit.
Note: The voltage at the STO input terminals of the drive must be at least 13 V DC to
be interpreted as “1”.
The pulse tolerance of the input channels is 1 ms.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control
unit at the control unit only.
Ground the shield in the cabling between two control units at one control unit
only.
The Safe torque off function 227

Table of Contents

Other manuals for ABB ACS580-04

Related product manuals