The Safe torque off function
Contents of this chapter
This chapter describes the Safe torque off (STO) function of the drive and gives
instructions for its use.
Description
The Safe torque off function can be used, for example, as the final actuator device of
safety circuits (such as an emergency stop circuit) that stop the drive in case of danger.
Another typical application is a prevention of unexpected start-up function that enables
short-time maintenance operations like cleaning or work on non-electrical parts of
the machinery without switching off the power supply to the drive.
When activated, the Safe torque off function disables the control voltage for the power
semiconductors of the drive output stage, thus preventing the drive from generating
the torque required to rotate the motor. If the motor is running when Safe torque off
is activated, it coasts to a stop.
The Safe torque off function has a redundant architecture, that is, both channels must
be used in the safety function implementation. The safety data given in this manual
is calculated for redundant use, and does not apply if both channels are not used.
The Safe torque off function complies with these standards:
NameStandard
Safety of machinery Electrical equipment of machines Part 1:
General requirements
IEC 60204-1:2016
EN 60204-1:2018
Electromagnetic compatibility (EMC) Part 6-7: Generic standards
Immunity requirements for equipment intended to perform functions
in a safety-related system (functional safety) in industrial locations
IEC 61000-6-7:2014