Installation procedure:
• Install the punched section to the back of the enclosure frame.
• Install the support rails and pedestal guide plate to the enclosure bottom frame.
• Install the telescopic extraction/installation ramp to the pedestal guide plate.
• Option +H370: Install the full-size input terminals.
• Install the fastening bracket to the drive module.
• Option +B051: Remove the sheeting from the clear plastic shrouds from both
sides.
• Option +B051: Install the bottom grille to the drive module if there is no bottom
plate in the enclosure and degree of protection of IP20 is needed for the drive
module from the bottom side.
• Option +B051: Install the top metallic shroud to the drive module.
• Option +B051: Install the back shrouds to the drive module.
• To prevent the drive module from falling, attach its lifting lugs with chains to the
cabinet frame.
• Push the drive module carefully into the enclosure along the telescopic
extraction/installation ramp.
• Remove the ramp.
• Attach the drive module to the pedestal guide plate.
• Attach the drive module from top to the punched section at the enclosure back.
Note: The fastening bracket grounds the drive module to the cabinet frame.
• Install the air baffles. For option +B051, refer to chapter Step-by-step drawings
for an installation example of a drive module with the +B051 option in a Rittal VX25
600 mm wide enclosure and section Air baffles for the drive module with option
+B051 (page 216). For the standard drive module configuration, see section Standard
drive module configuration (page 56).
Connecting the power cables and installing the shrouds
Task (motor cables)Step
Install the grounding terminal to the drive module base.1
Run the motor cables to the enclosure. Ground the cable shields 360° at the cabinet entry.2
Connect the twisted shields of the motor cables to the grounding terminal.3
Screw in and tighten the insulators to the drive module by hand. Install the T3/W2 connection
terminal to the insulators.
4
WARNING!
Do not use longer screws or a larger tightening torque than specified in the in-
stallation drawing. They can damage insulator and cause a dangerous voltage
to be present at the module frame.
Connect the phase T3/W2 conductors to the T3/W2 terminal.5
Install the T2/V2 connection terminal to the insulators See the warning in step 4.6
Installation example of drive module with IP20 shrouds (option +B051) 115