Losses, cooling data and noise
Noise
Typical power
loss
1)
Air flow
Frame
size
ACS580-04…
Wcfmm
3
/h dB(A)
7264927071200R10505A-4
7268407071200R10585A-4
7280467071200R10650A-4
7281087071200R11725A-4
7296527071200R11820A-4
71108878481420R11880A-4
1)
Typical drive losses when it operates at 90% of the motor nominal frequency and 100% of the motor nominal
current.
Terminal and entry data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM). Screw
size for connecting busbars to the drive module input and output busbars: M12,
tightening torque 50…75 N·m (37…55 lbf·ft).
■ Drive modules without output cable connection terminals (+0H371)
and with a common mode filter (+E208)
It is possible to use the maximum cable size 4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM)
only with special cable lugs and additional insulation. For more information, contact
your local ABB representative.
■ Drive modules with optional cabling panels (+H381)
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM). The
cabling panels are connected to the drive module busbars with M12 serpress nuts,
tightening torque 30 N·m (20 lbf·ft).
Technical data 187