EasyManua.ls Logo

ABB ACS580-04 - Connection Examples of Two-Wire and Three-Wire Sensors to Analog Input (AI2); Connection for Obtaining 0; NPN Configuration for Digital Inputs (X2 & X3)

ABB ACS580-04
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NPN configuration for digital inputs (X2 & X3)
Internal and external +24 V power supply connections for NPN configuration are shown
in the figure below.
External +24 V power supply
NPN connection (sink)
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
0 V DC
+24 V DC
Internal +24 V power supply
NPN connection (sink)
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
Note: DI6 is not supported in the NPN configuration.
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.
Connection for obtaining 0…10 V from analog output 2 (AO2)
To obtain 0…10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between analog output AO2 and analog common ground AGND.
X1
8AO2
9AGND
500 ohm
X1
8AO2
9AGND
1kohm 1kohm
0…10 V
0…10 V
Connection examples of two-wire and three-wire sensors to analog
input (AI2)
Note: The maximum capability of the auxiliary voltage output (24 V DC [250 mA]) must
not be exceeded.
An example of a two-wire sensor/transmitter supplied by the drive auxiliary voltage
output is shown below. Set the input signal to 4…20 mA, not 0…20 mA.
4…20 mA
+
-
P
I
...
AI2
AGND
+24V
DGND
140 Control unit

Table of Contents

Other manuals for ABB ACS580-04

Related product manuals