DefaultSettingParameter
No actionFault32.06 Supervision 1 action
FrequencyAI132.07 Supervision 1 signal
0.000.432.09 Supervision 1 low
Diagnostics
LEDs
The adapter module has one diagnostic LED.
DescriptionColor
The adapter module is powered up.Green
Technical data
Into SLOT 2 on the drive control unitInstallation
IP20Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Analog inputs (80…82, 83…85)
1.5 mm
2
Maximum wire size
-10 V +10 VInput voltage (AI+ and
AI-)
> 200 kohmInput resistance
Optional cable shield connection
Analog outputs (86…88, 89…91)
1.5 mm
2
Maximum wire size
0 V +10 VOutput voltage (AO+ and
AGND)
< 20 ohmOutput resistance
> 10 kohmRecommended load
typical ±1%, max. ±1.5% of full scaleInaccuracy
Optional cable shield connection
Analog output scale switch
0.5 V 9.5 V range in useON state
0 V …10 V range in useOFF state
Isolation areas
258 CBAI-01 bipolar analog IO adapter module