Start-up
Contents of this chapter
This chapter describes the start-up procedure of the drive.
Reforming the capacitors
The capacitors must be reformed if the drive has not been powered (either in storage
or unused) for a year or more. The manufacturing date is on the type designation label.
For information on reforming the capacitors, refer to Capacitor reforming instructions
(3BFE64059629 [English]).
Start-up procedure
1. Make sure that the installation of the drive module has been checked according
to the checklist in chapter Installation checklist (page 159), and that the motor and
driven equipment are ready for start.
2. Perform the start-up tasks instructed by the cabinet-installer of the drive module.
3. Run setup of the drive control program according to the start-up instructions
given in the quick start-up guide or firmware manual.
4. For drives with option +D150, see chapter Resistor braking (page 241).
5. For drive modules in which the Safe torque off function is in use: Test and validate
the operation of the Safe torque off function. See section Start-up including
validation test (page 229).