Default I/O connection diagram
Default I/O connection diagram
The default I/O connections of the ABB Standard macro are shown below.
DescriptionTermConnection
X1 Reference voltage and analog inputs and outputs
Signal cable shield (screen)SCR1
1
2
3
4
5
6
7
8
9
1...10 kohm
Max.
500 ohm
8)
Output frequency reference: 0…10 V
1) 3)
AI12
Analog input circuit commonAGND3
Reference voltage 10 V DC+10V4
Not configuredAI25
Analog input circuit commonAGND6
Output frequency: 0…20 mAAO17
Motor current: 0…20 mAAO28
Analog output circuit commonAGND9
X2 & X3 Aux. voltage output and programmable digital inputs
Aux. voltage output +24 V DC, max. 250 mA
2)
+24V10
10
11
12
13
14
15
16
17
18
6)
7)
Aux. voltage output commonDGND11
Digital input common for allDCOM12
Stop (0) / Start (1)DI113
Forward (0) / Reverse (1)DI214
Constant frequency selection
4)
DI315
Constant frequency selection
4)
DI416
Ramp set 1 (0) / Ramp set 2 (1)
5)
DI517
Not configuredDI618
X6, X7, X8 Relay outputs
Ready runRO1C19
19
20
21
22
23
24
25
26
27
Ready run status
Run status
Fault status
250 V AC / 30 V DC
2 A
RO1A20
RO1B21
Running
250 V AC / 30 V DC
2 A
RO2C22
RO2A23
RO2B24
Fault (-1)
250 V AC / 30 V DC
2 A
RO3C25
RO3A26
RO3B27
X5 EIA-485 Modbus RTU
Embedded Modbus RTU (EIA-485)
B+29
29
30
31
S4
S5
A-30
DGND31
Serial data link termination switchTERMS4
Serial data link bias resistors switchBIASS5
X4 Safe Torque Off
Control unit 137