DescriptionTermConnection
Safe torque off. Factory connection. Both
circuits must be closed for the drive to
start.Refer to The Safe torque off func-
tion (page 221).
OUT134
34
35
36
37
38
6)
6)
OUT235
SGND36
IN137
IN238
X10 24 V AC/DC
External 24 V AC/DC input to power up the
control unit when the main supply is discon-
nected.
9)
24 V
AC/DC+ in
40
40
41
24 V
AC/DC- in
41
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Digital inputs DI1…DI5 also support 10…24 V AC.
Terminal sizes (all terminals): 0.14 2.5 mm
2
(26…14 AWG)
Tightening torques: 0.5 0.6 N·m (4.4 5.3 lbf·in)
Wire strip length 7…8 mm (0.3 in)
Notes:
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
>200 kohm]. Change of setting
requires changing the corresponding parameter.
1)
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V) minus the
power taken by the option modules installed on the board.
2)
AI1 is used as a speed reference if vector control is selected.3)
In scalar control (default): See Menu > Primary settings > Start, stop, reference > Constant fre-
quencies or parameter group 28 Frequency reference chain.
4)
In vector control: See Menu > Primary settings > Start, stop, reference > Constant speeds or
parameter group 22 Speed reference selection
Operation/ParameterDI4DI3
Vector controlScalar control (default)
Set speed through AI1Set frequency through AI100
22.26 Constant speed 128.26 Constant frequency 101
22.27 Constant speed 228.27 Constant frequency 210
22.28 Constant speed 328.28 Constant frequency 311
In scalar control (default): See Menu - Primary settings - Ramps or parameter group 28 Frequency
reference chain.
5)
In vector control: See Menu - Primary settings - Ramps or parameter group 23 Speed reference
ramp.
ParametersRamp
set
DI5
Vector controlScalar control (default)
23.12 Acceleration time 1
23.13 Deceleration time 1
28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
10
23.14 Acceleration time 2
23.15 Deceleration time 2
28.74 Freq acceleration time 2
28.75 Freq deceleration time 2
21
138 Control unit