Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper shield
for the drives with nominal current. See also section Terminal and entry data for the
power cables (page 187).
IEC
1)
ACS580-04-…
Al cableCu cable
mm
2
mm
2
U
n
= 400 V
3 × (3×150)3 × (3×95)505A-4
3 × (3×185)3 × (3×120)585A-4
3 × (3×240)3 × (3×150)650A-4
4 × (3×185)3 × (3×185)725A-4
4 × (3×240)3 × (3×240)820A-4
4 × (3×240)3 × (3×240)880A-4
U
n
= 480 V
3 × (3×150)3 × (3×95)505A-4
3 × (3×150)3 × (3×95)585A-4
3 × (3×185)3 × (3×120)650A-4
3 × (3×240)3 × (3×150)725A-4
4 × (3×185)3 × (3×185)820A-4
4 × (3×240)3 × (3×240)880A-4
1)
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of
the other, ambient temperature 30 °C PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.