the conductors to the R+ and R- terminals. For the tightening torques, see the
technical data.
5. Make sure that all power is disconnected and reconnection is not possible. Use
proper safe disconnect procedures according to local codes.
6. Run the input cables from the supply source to the enclosure. Ground the cable
shields 360° at the entry plate.
7. Twist the cable shields of the input cables into bundles and connect them and
any separate ground conductors or cables to grounding busbar of the input cabling
panel.
8. Connect the phase conductors of the input cables to terminals L1/U1, L2/V1 and
L3/W1 of the drive module. For the tightening torques, see the technical data.
C
A
A
B
C
D
102 mm (4 in.)
L1/U1, L2/V1, L3/W1
T1/U2, T2/V2, T3/W2
E
E
View without cabinet side plate in place.
360-degree grounding at the entry plate for the input power cablesA
Grounding busbar of the input power cabling panelB
360-degree grounding at the entry plate for the output power cablesC
124 Installation example with full cabling panels (option +H381)