WARNING!
Obey these instructions. If you ignore them, equipment malfunction and
damage to the fiber optic cables can occur.
Handle the fiber optic cables with care.
When you unplug the cables, always hold the connector, not the cable
itself.
Do not touch the ends of the fibers with bare hands as the ends are
extremely sensitive to dirt.
Do not bend the fiber optic cables too tightly. The minimum allowed
bend radius is 35 mm (1.4 in).
ZBIBDrive module
M4×8 Torx T20
2 N·m (18 lbf·in)
ZPOW
BGDR
SOIA
ZPOW
X3:1X3:1
X3:2X3:2
BGDR
X7 (STO1)X7 (STO1)
X8 (STO2)X8 (STO2)
SOIA
V1V10
V2V20
4. Connect the ground connection at the drive module end.
156 External control unit (option +P906)