6. Prepare the ends of the cables.
WARNING!
Apply grease to stripped aluminum conductors before attaching them to
non-coated aluminum cable lugs. Obey the grease manufacturer’s instructions.
Aluminum-aluminum contact can cause oxidation in the contact surfaces.
PE
PE
7. If fire insulation is used, make an opening in the mineral wool sheet according to the
diameter of the cable.
8. Put the cables through the bottom plate.
9. Remove rubber grommets from the bottom plate for the cables to be connected. Cut
adequate holes into the rubber grommets. Slide the grommets onto the cables. Slide
the cables through the bottom plate with the conductive sleeves and attach the grommets
to the holes.
10. Attach the conductive sleeves to the cable shields with cable ties. Tie up the unused
conductive sleeves with cable ties.
11. Seal the slot between the cable and mineral wool sheet (if used) with sealing compound
(eg, CSD-F, ABB brand name DXXT-11, code 35080082).