1500 m
1000 m
+25 °C +30 °C
+77 °F +86 °F
+40 °C
+104 °F
+35 °C
+95 °F
+20 °C
+68 °F
3300 ft
4921 ft
2000 m
6562 ft
2500 m
8202 ft
3000 m
9842 ft
3500 m
11429 ft
4000 m
13123 ft
1.00
0.95
0.85
0.90
0.80
Derating factor 1.00
Derating factor 0.95
Derating factor 0.90
Derating factor 0.85
Derating factor 0.80
For a more accurate derating, use the DriveSize PC tool.
Inverter modules used, DC fuses, and DC capacitances
DC
capacitance
Module DC fuse type and quantity
Module type and
quantity
Unit type
μFQtyTypeQty
ACS880-
104-…
ACS880-
107-…
U
n
= 400 V
2802
Eaton Bussmann FWP-10A14F
1)
1004A8-3004A8-3
2802Eaton Bussmann FWP-15A14F
1)
1006A0-3006A0-3
2802Eaton Bussmann FWP-15A14F
1)
1008A0-3008A0-3
4352Eaton Bussmann FWP-20A14F
1)
10011A-30011A-3
8652Eaton Bussmann FWP-25A14F
1)
10014A-30014A-3
8652Eaton Bussmann FWP-32A14F
1)
10018A-30018A-3
7852Mersen 6.921 CP URQ 27x60/50
1)
10025A-30025A-3
7852Mersen 6.921 CP URQ 27x60/63
1)
10035A-30035A-3
11782Mersen 6.921 CP URQ 27x60/80
1)
10044A-30044A-3
11782Mersen 6.921 CP URQ 27x60/100
1)
10050A-30050A-3
146 Technical data