Energy efficiency data (ecodesign)
Energy efficiency data is not provided for the drive/unit. Multidrives and multidrive
modules are not in the scope of the EU ecodesign requirements (Regulation
EU/2019/1781) or the UK ecodesign requirements (Regulation SI 2021 No. 745).
Protection classes
IP22 (standard), IP42 (option +B054), IP54 (option +B055)Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 1 (option +B054), UL Type 12 (option +B055).
For indoor use only.
Enclosure types (UL50)
B – ASSEMBLY providing personnel and ASSEMBLY protection under arcing
conditions.
Tested at the following voltage with an arcing current of 65 kA for 300 milli-
seconds:
Arcing class
(IEC TR 61641)
• 400 V units (indicated by "-3" in drive type): 420 V
• 500 V units (indicated by "-5" in drive type): 550 V
• 690 V units (indicated by "-7" in drive type): 760 V
III, except for auxiliary power connections (fan, control, heating, lighting etc)
which are category II.
Overvoltage category
(IEC/EN 60664-1)
IProtective class
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective pack-
age
Storage
in the protective pack-
age
Operation
installed for stationary
use
--0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, con-
tact ABB.
Installation site altitude
Output derated above
1000 m (3281 ft).
-40 … +70 °C-40 … +70 °C0 … +40 °C
(+32 … +104 °F). No con-
densation allowed.
Air temperature
(-40 … +158 °F)(-40 … +158 °F)
Output derated in the
range +40 … +50 °C
(+104 … +122 °F).
For UL and CSA compli-
ant installations, the
maximum surrounding
air temperature is 40 °C
(104 °F).
Max. 95%Max. 95%Max. 95%Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.