*Contact your local ABB representative for availability and technical data of sine filters.
**Maximum value with direct-on-line cooling fan.
Sine output filter data
Sine output filters are available as option +E206. The table below shows the types and
technical data of the filters and filter cubicles used. The standard filters listed require
no current derating.
For availability of sine output filters for other inverter unit types, contact your local
ABB representative.
Cooling dataDimensions
Nominal
current
Sine filter(s) used
Inverter unit
type ACS880-
107…
Air flow
Heat
dissipation
weightWidth
TypeQty
m
3
/h (cfm)kWkg (lbs)mmA
U
n
= 400 V
See Noise and cooling charac-
teristics (page 150)
840 (1850)1000783NSIN-0900-610470A-3
840 (1850)1000783NSIN-0900-610640A-3
840 (1850)1000783NSIN-0900-610760A-3
960 (2120)10001201NSIN-1380-610900A-3
1680 (3700)20001488NSIN-0900-621250A-3
1680 (3700)20001488NSIN-0900-621480A-3
1920 (4230)20002282NSIN-1380-621760A-3
1920 (4230)20002282NSIN-1380-622210A-3
2880 (6350)30003387NSIN-1380-632610A-3
2880 (6350)30003387NSIN-1380-633450A-3
3840 (8470)40004468NSIN-1380-644290A-3
4800 (10580)50005525NSIN-1380-655130A-3
U
n
= 500 V
See Noise and cooling charac-
teristics (page 150)
340 (750)400447NSIN-0485-610440A-5
840 (1850)1000783NSIN-0900-610590A-5
840 (18501000783NSIN-0900-610740A-5
960 (2120)10001201NSIN-1380-610810A-5
960 (2120)10001201NSIN-1380-611150A-5
1680 (3700)20001488NSIN-0900-621450A-5
1920 (4230)20002282NSIN-1380-621580A-5
1920 (4230)20002282NSIN-1380-622150A-5
2880 (6350)30003387NSIN-1380-632350A-5
2880 (6350)30003387NSIN-1380-633110A-5
3840 (8470)40004468NSIN-1380-643860A-5
4800 (10580)50005525NSIN-1380-654610A-5
Technical data 153