0…500 HzFrequency (f2)
0…120 Hz with sine output filters (option +E206)
0…120 Hz for frames R1i…R5i with du/dt filters (option +E205)
0…200 Hz for frames R6i and R7i with du/dt filters (option +E205)
For higher operational output frequencies, contact your local ABB repres-
entative.
Operation at frequencies higher than 150 Hz can require derating. For more
information, contact your local ABB representative.
Refer to the technical data.Current
Frames R1i…R4i: 4.5 kHz (typical)Switching frequency
Frames R5i…R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values,
contact your local ABB representative.
Frames R1i…R2i: 150 m (492 ft)
1)
Maximum recommended
motor cable length
Frames R3i…R7i: 300 m (984 ft)
1)
Frame R8i and multiples: 500 m (1640 ft)
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and charac-
teristics. Contact ABB for more information. A sine filter (optional) at the
drive output also causes a voltage decrease.
Refer to section Terminal and cable entry data for the power cables (page 156).Output terminals
1)
Tested with 100 m (328 ft) for EMC Category C3. See standards and markings information in ACS880 multidrive
cabinets and modules electrical planning instructions (3AUA0000102324 [English]).
Typical power cable sizes
The tables below give the current carrying capacity (
I
Lmax
) and typical size for copper
and aluminum cables with PVC or XLPE insulation. A correction factor K = 0.70 is used.
Time const. is the temperature time constant of the cable.
The cable sizing is based on a maximum of 9 cables installed side by side on a ladder
type cable tray, with three trays on top of each other (with 30 cm of space between
the trays), and an ambient temperature of 30 °C (IEC 60364-5-52).
Typical dimensions of copper
cable
XLPE insulation
Conductor temperat-
ure 90°
PVC insulation
Conductor temperat-
ure 70°
Conductor cross-sec-
tion (copper)
ø [mm]SizeTime
const. (s)
I
Lmax
(A)Time
const. (s)
I
Lmax
(A)AWG /
kcmil
mm
2
133 × 1.5 + 1.567168513161.5
143 × 2.5 + 2.5882312118122.5
163 × 4 + 41333017524124
183 × 6 + 61863825130106
213 × 10 + 102685335942810
233 × 16 + 163917051456616
243 × 25 + 165988979171425
263 × 35 + 16760110100088135
293 × 50 + 2599013413081071/050
323 × 70 + 35123017116131372/070
Technical data 155