3. Cut the cable to suitable length and strip the ends of the individual conductors.
4. Twist the shield strands of the cable together to form a separate conductor and
crimp a ferrule onto it. (With frame R4i, connect the cable shield to the PE busbar
using a crimp ring terminal.)
5. Connect the conductors to terminal block/connector X1. (If X1:4 is not present,
connect the cable shield directly to the PE busbar.) See Drives cabinets_Connecting
cable lug to a busbar.xml.
6. Secure the cable inside the cabinet mechanically.
7. Tighten the cable gland.
8. At the motor, connect the cables according to instructions from the motor
manufacturer. Pay special attention to the phase order. For minimum
radio-frequency interference, ground the cable shield 360° at the cable entry of
the motor terminal box.
48 Electrical installation