Accessories
124
3ADW000194R0611 DCS800 Hardware Manual f us
Line reactors IEC
Line reactors type ND 01...ND 17
Line reactors (u
k
= 1%) for use in industrial environment (minimum requirements), low inductive voltage
drop, deep commutation notches.
Line reactors ND01...ND06 are equipped with cables. The bigger ones ND07...ND16 are equipped with
busbars. When connecting them to other components, please take relevant standards into account in
case the materials are different. Don't use reactor terminals as cable or busbar support!
Frequency 50 / 60 Hz
Line reactors type ND 01...ND 06
Type reactor rated Weight Power loss recommended
L I
rms
I
peak
Voltage Fe Cu for armature
[μH] [A] [A] [U
N
] [kg] [W] [W] converter type
ND 01 512 18 27 500 2.0 5 16 DCS...-0025
ND 02 250 37 68 500 3.0 7 22 DCS...-0050
ND 03 300 37 68 600 3.8 9 20 DCS...-0050
ND 04 168 55 82 500 5.8 10 33 DCS...-0075
ND 05 135 82 122 600 6.4 5 30 DCS...-0110
ND 06 90 102 153 500 7.6 7 41 DCS...-0140
ND 07 50 184 275 500 12.6 45 90 DCS...-0250
ND 08 56.3 196 294 600 12.8 45 130 DCS...-0270
ND 09 37.5 245 367 500 16.0 50 140 DCS...-0350
ND 10 25.0 367 551 500 22.2 80 185 DCS...-0520
ND 11 33.8 326 490 600 22.6 80 185 DCS...-0450
ND 12 18.8 490 734 500 36.0 95 290 DCS...-0680
ND 13 18.2 698 1047 690 46.8 170 160 DCS...-0820
ND 14 9.9 930 1395 500 46.6 100 300 DCS...-1200
ND 15 10.9 1163 1744 690 84.0 190 680 DCS...-1500
ND 16 6.1 1510 2264 500 81.2 210 650 DCS...-2000
ND 17 4.0 1800 2700 800 86.0 250 700 DCS...-2500
A, B, C
6
0
0
1
0
0
0
X, Y, Z
b
a
a1
c
A
X
B
Y
C
Z
A
B
C
X
Y
Z
3
A, B, C
X, Y, Z
d
e
g
f
ND1_to_6_a.dsf
Typea1abcdefg
mm²
ND 01 120 100 130 48 65 116 4 8 6
ND 02 120 100 130 58 65 116 4 8 10
ND 03 148 125 157 63 80 143 5 10 10
ND 04 148 125 157 78 80 143 5 10 16
ND 05 148 125 157 78 80 143 5 10 25
ND 06 178 150 180 72 90 170 5 10 35