Accessories
127
3ADW000194R0611 DCS800 Hardware Manual f us
Line reactors type ND 401...ND 413
Line reactors (u
k
= 4%) for use in light industrial/residential environment, high inductive voltage drop,
reduced commutation notches.
These reactors are designed for drives which usually operate in speed control mode at 400 V or 500 V
networks. Because of that a duty cycle has been taken into account. The percentage taken into account
for that duty cycle is different for 400 V and 500 V networks:
-for U
rated supply
= 400 V, DC curr. 1 = 90% of nominal current
-for U
rated supply
= 500 V, DC curr. 2 = 72% of nominal current
For easier reading the maximum average DC load current is listed instead of the percentage in the next
table.
Line reactors ND401...ND402 are equipped with terminals. The bigger ones ND403...ND413 are
equipped with busbars. When connecting them to other components, please take relevant standards
into account in case the materials are different.
Frequency 50 / 60 Hz
Line reactors type ND 401...ND 402
Type reactor rated Weight Power loss Load Load
L I
rms
I
peak
Voltage Fe Cu DC curr. 1 DC curr.2
[μH] Line AC [A] [A] [U
N
][kg] [W] [W](f. U
supply
=400V) (f. U
supply
=500V)
ND 401 1000 18.5 27 400 3.5 13 35 22.6 18
ND 402 600 37 68 400 7.5 13 50 45 36
ND 403 450 55 82 400 11 42 90 67 54
ND 404 350 74 111 400 13 78 105 90 72
ND 405 250 104 156 400 19 91 105 127 101
ND 406 160 148 220 400 22 104 130 179 143
ND 407 120 192 288 400 23 117 130 234 187
ND 408 90 252 387 400 29 137 160 315 252
ND 409 70 332 498 400 33 170 215 405 324
ND 410 60 406 609 400 51 260 225 495 396
ND 411 50 502 753 400 56 260 300 612 490
ND 412 40 605 805 400 62 280 335 738 590
ND 413 35 740 1105 400 75 312 410 900 720
Type ABCDEFØ GØ H
ND 401 160 190 75 80 51 175 7 9
ND 402 200 220 105 115 75 200 7 9
A
X
B
YC
Z
170
D
B
F±1
ø G+5
E ±2
C
Z
Y
X
B
AC
Terminals: WAGO Type 202
UL File E45172
ø H
A
ø G
tin-coated