Planning the electrical installation
53
3ADW000194R0611 DCS800 Hardware Manual f us
Connection of a motor temperature sensor to the drive I/O
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfill this requirement, the connection of a thermistor (and other similar
components) to the inputs of the drive can be implemented by three alternate ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive.