Planning the electrical installation
43
3ADW000194R0611 DCS800 Hardware Manual f us
Converters D1...D3 3-phase field exciter configuration
Wiring the drive according to this diagram offers the highest degree of monitoring
functions done by the drive.
further information see drawing at page 43
SDCS-DSL
X52:
X53:
GNDB
S2
123321
IN3
OUT3
IN1
OUT1
V5
V6
V1
V2
X96:
DO8
12 X99:12 X2:123
U1 W1V1 PE
K1
X96:1
X96:2
L1 L2 L3
F1
M
~
F2
3
4
1
2
T2
690V
660V
600V
575V
525V
500V
450V
415V
400V
380V
115V
230V
K15
K15
S1
1
2
K8
K1
X33
C 1 D 1
AITAC AI1
AI2 AI3
AI4
+10V -10V AO1 AO2 IACT DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 +24V DO1 DO2 DO3 DO4 DO5 DO6 DO7
____
_
++++
+
0V
0V0V0V0V
X3:12345678910X4:12345678910X6:12345678910
X7:
1234 56 7 8 1...10
X5:
+
_
K1
1
2
S1
S1
56
F5
1
2
F8
1
2
F7
1
2
K1
135
246
L1
1
2
3
4
K8
X10:
F+ F-
21
L1 L2
DCS8_ans_1_4a.dsf
DCS800
*
PIN-4
DCF506
X11 X12
X14:
1
2
Communication
board (COM-8x)
Control board (CON-4)
Power supply
Converter
module
EMER.
STOP
'on board' field exciter
depending on the unit type
an other configuration is possible
Voltage levels
see description
control from
armature converter
Overvoltage
protection
If stop category 1 (E-STOP ramp)
is required don't connect E-STOP
command to field exciter (K15).
Use COAST command of
armature converter as input K15
<E-STOP mode> should be
selected to COAST. It can take up
to more than one second to
remove field current from
converter (time delay K15)
K1 can also be controlled from armature converter
If installation is not equipped with K1 and converter
is direct supplied from high voltage transformer
additional overvoltage protection is required.
disabled by parameter or not
selected (plus code +0S163)
Legend
fuse
reactor