Safety instructions
6
3ADW000194R0611 DCS800 Hardware Manual f us
Installation and maintenance work
These warnings are intended for all who work on the drive, motor cable or motor.
Ignoring the instructions can cause physical injury or death.
Only qualified electricians are allowed to install and maintain the drive.
Never work on the drive, motor cable or motor when main power is applied.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. Voltage between drive input phases U1, V1 and W1 and the frame is close to
0V.
2. Voltage between terminals C1 and D1 and the frame is close to 0 V.
Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
Do not make any insulation or voltage withstand tests on the drive or drive
modules.
When reconnecting the motor cable, always check that the C1 and D1 terminal
is correct.
Note:
The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
may be present on the terminals of relay outputs SDCS-IOB-2, RDIO.
DCS800 with enclosure extension: Before working on the drive, isolate the
whole drive from the supply.

Table of Contents

Other manuals for ABB DCS800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS800 and is the answer not in the manual?

ABB DCS800 Specifications

General IconGeneral
Control TypeDigital
Supply Voltage380 ... 690 V AC
Input Voltage Range380 V to 690 V AC
Control ModeTorque, Speed
Cooling MethodAir-cooled
Communication ProtocolsModbus, Profibus, CANopen
Communication OptionsEthernet
Protection ClassIP21, IP54
Enclosure RatingIP00, IP21, IP54
ProtectionOvercurrent, Overvoltage, Overtemperature
Ambient Temperature0 to 40°C
Field SupplyIntegrated or External