Planning the electrical installation
50
3ADW000194R0611 DCS800 Hardware Manual f us
Cross-sectional areas - Tightening torques
Recommended cross-sectional area to DINVDE 0276-1000 and DINVDE 0100-540
(PE) trefoil arrangement, up to 50°C ambient temperature. The necessary wire torque at
60°C wire temperature is the same as recommended in the following tables.
Armature:
➀Reduced ambient temperature 40°C
➁Option for more flexible cable connection available
You will find instructions on how to calculate the PE conductor’s cross-sectional area
in VDE 0100 or in equivalent national standards. We would remind you that power
converters may have a current-limiting effect.
Excitation:
Converter type C1, D1 (AM1, KM1) U1, V1, W1(AK1, AK3, AK5) PE
[Nm]
IDC
[A-]
1
[mm²]
(2.)
[mm²]
Iv
[A~]
1
[mm²]
(2.)
[mm²] [mm²]
DCS800-S0x-0025-xx 25 1 x 6 - 41 1 x 4 - 1x 4 1 x M6 6
DCS800-S0x-0050-xx 50 1 x 10 - 41 1 x 6 - 1x 6 1 x M6 6
DCS800-S0x-0075-xx 75 1 x 25 - 61 1 x 25 - 1x 16 1 x M6 6
DCS800-S0x-0100-xx 100 1 x 25 - 82 1 x 25 - 1x 16 1 x M6 6
DCS800-S0x-0140-xx 140 1 x 35 - 114 1 x 35 - 1x 16 1 x M6 6
DCS800-S0x-0200-xx 200 2 x 35 1 x 95 163 2 x 25 1 x 95 1x 25 1 x M10 25
DCS800-S0x-0260-xx 260 2 x 35 1 x 95 204 2 x 25 1 x 95 1x 25 1 x M10 25
DCS800-S0x-0320-xx 320 2 x 70 1 x 95 220 2 x 50 1 x 95 1x 50 1 x M10 25
DCS800-S0x-0350-xx 350 2 x 70 - 286 2 x 50 1x 50 1 x M10 25
DCS800-S0x-0450-xx 450 2 x 95 - 367 2 x 95 - 1x 50 1 x M10 25
DCS800-S0x-0520-xx 520 2 x 95 - 424 2 x 95 - 1x 50 1 x M10 25
DCS800-S0x-0650-xx 650 2 x 120 - 555 2 x 120 - 1x120 1 x M12 50
DCS800-S0x-0680-xx 680 2 x 120 - 555 2 x 120 - 1x120 1 x M12 50
DCS800-S0x-0820-xx 820 2 x 150 - 669 2 x 120 - 1x120 1 x M12 50
DCS800-S0x-0900-6/7 900 4 x 95 3 x 150 734 4 x 70 3 x 95 1x150 2 x M12 50
DCS800-S0x-1000-xx 1000 2 x 185 - 816 2 x 150 - 1x150 1 x M12 50
DCS800-S0x-1200-xx 1200 4 x 120 - 979 4 x 95 3 x 120 1x185 2 x M12 50
DCS800-S0x-1500-xx 1500 4 x 185 - 1224 4 x 150 - 2x150 2 x M12 50
DCS800-S0x-2000-xx 2000 8 x 120 6 x 185 1632 4 x 240 - 2x240 2 x M12 50
DCS800-S0x-1900-xx ➁ 1900 8 x 120 6 x 185 1550 4 x 240 3x120 4 x M12 50
DCS800-S0x-2050-xx ➁ 2050 8 x 120 6 x 185 1673 6 x 120 5 x 150 3x120 4 x M12 50
DCS800-S0x-2500-xx ➁ 2500 7 x 185 - 2040 8 x 120 6 x 185 4x120 4 x M12 50
DCS800-S0x-2600-xx 2600 7 x 185 - 2122 8 x 120 6 x 185 4x120 4 x M12 50
DCS800-S0x-3000-xx ➁ 3000 8 x 185 - 2448 7 x 185 - 4x150 4 x M12 50
DCS800-S0x-3300-xx 3300 8 x 185 - 2693 7 x 185 - 4x150 4 x M12 50
DCS800-S0x-4000-xx 4000 7 x 300 - 3264 8 x 240 - 4x240 4 x M12 50
DCS800-S0x-4800-xx ➀ 4800 8 x 300 - 3876 6 x 300 - 3x300 4 x M12 50
DCS800-S0x-5200-xx ➀ 5200 8 x 300 - 4202 6 x 300 - 3x300 4 x M12 50
Size D1 D2 D3 D4 D5 DCF803-0035
DC output current 6 A 15 A 20 A 25 A 25 A 35 A
max. cross sectional area 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10
min. cross sectional area 1 mm²/ AWG 16 2.5 mm²/ AWG 13 4 mm²/ AWG 11 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10
Tightening torque 1.5...1.7 Nm