8.3.5 Settings
Table 79: ROV2PTOV (59N) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
OperationStep1 Disabled
Enabled
- - Enabled Enable execution of step 1
Characterist1 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
- - Definite time Selection of time delay curve type for step 1
Pickup1 1 - 200 %VB 1 30 Voltage start value (DT & IDMT) in % of
VBase for step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definite time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves for
step 1
TD1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay for
step 1
OperationStep2 Disabled
Enabled
- - Enabled Enable execution of step 2
Pickup2 1 - 100 %VB 1 45 Voltage start value (DT & IDMT) in % of
VBase for step 2
t2 0.000 - 60.000 s 0.001 5.000 Definite time delay of step 2
Table 80: ROV2PTOV (59N) Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
8.3.6 Monitored data
Table 81: ROV2PTOV (59N) Monitored data
Name
Type Values (Range) Unit Description
VLevel REAL - kV Magnitude of measured
voltage
8.3.7 Operation principle
Two step residual overvoltage protection ROV2PTOV (59N) is used to detect ground
(zero sequence) overvoltages. The ground overvoltage 3V
0
is normally computed by
1MRK 505 277-UUS C Section 8
Voltage protection
139