Name Type Description
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16
11.8.5 Settings
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
11.8.6 Operation principle
Integer to boolean conversion with logic node representation function (IB16FCVB) is
used to transform an integer into a set of 16 binary (logical) signals. IB16FCVB
function can receive an integer from a station computer – for example, over IEC
61850. The BLOCK input will freeze the logical outputs at the last value.
The operator position input (PSTO) determines the operator place. The integer number
can be written to the block while in “Remote”. If PSTO is in ”Off” or ”Local”, then no
change is applied to the outputs.
1MRK 505 277-UUS C Section 11
Logic
215
Technical Manual