12.3.2.2 Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
IEC09000346 V1 EN
Figure 110: DRPRDRE function block
12.3.2.3 Signals
Table 214: DRPRDRE Output signals
Name Type Description
DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used
12.3.2.4 Settings
Table 215: DRPRDRE Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
PreFaultRecT 0.05 - 3.00 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 8.0 s 0.1 1.0 Fault recording time limit
PostRetrig Disabled
Enabled
- - Disabled Post-fault retrig enabled (On) or not (Off)
MaxNoStoreRec 10 - 100 - 1 100 Maximum number of stored disturbances
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference channel
OpModeTest Disabled
Enabled
- - Disabled Operation mode during test mode
Section 12 1MRK 505 277-UUS C
Monitoring
252
Technical Manual