12.14.2 Function block
SPVNZBAT
V_BATT
BLOCK
AL_VLOW
AL_VHI
PU_VLOW
PU_VHI
ANSI12000026-1-en.vsd
ANSI12000026 V1 EN
Figure 123: Function block
12.14.3 Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
SPVNZBAT activates the start and alarm outputs when the battery terminal voltage
exceeds the set upper limit or drops below the set lower limit. A time delay for the
overvoltage and undervoltage alarms can be set according to definite time characteristics.
In the definite time (DT) mode, SPVNZBAT operates after a predefined operate time
and resets when the battery undervoltage or overvoltage condition disappears after
reset time.
12.14.4 Signals
Table 250: SPVNZBAT Input signals
Name
Type Default Description
V_BATT REAL 0.00 Battery terminal voltage that has to be supervised
BLOCK BOOLEAN 0 Blocks all the output signals of the function
Table 251: SPVNZBAT Output signals
Name
Type Description
AL_VLOW BOOLEAN Alarm when voltage has been below low limit for a set
time
AL_VHI BOOLEAN Alarm when voltage has exceeded high limit for a set
time
PU_VLOW BOOLEAN Pick up signal when battery voltage drops below lower
limit
PU_VHI BOOLEAN Pick up signal when battery voltage exceeds upper limit