12.16.4.2 SSIML OutputSignals
Table 261: Output signals for the function block SSIML (LM1-)
Signal Description
LEVEL Level service value
LVL_ALM Level below alarm level
LVL_LO Level below lockout level
TEMP Temperature of the insulation medium
TEMP_ALM Temperature above alarm level
TEMP_LO Temperature above lockout level
12.16.5 Settings
12.16.5.1 SSIML Settings
Table 262: Basic parameter group settings for the function SSIML (LM1-)
Parameter Range Step Default Unit Description
Operation Off
On
- Off - Operation Off / On
LevelAlmLimit 0.00 - 25.00 0.01 5.00 - Alarm setting for level
LevelLOLimit 0.00 - 25.00 0.01 3.00 - Level lockout setting
TempAlarmLimit -40.00 - 200.00 0.01 30.00 - Temperature alarm level
setting of the medium
TempLOLimit -40.00 - 200.00 0.01 30.00 - Temperature lockout
level of the medium
tLevelAlarm 0.000 - 60.000 0.001 0.000 s Time delay for level alarm
tLevelLockOut 0.000 - 60.000 0.001 0.000 s Time delay for level
lockout indication
tTempAlarm 0.000 - 60.000 0.001 0.000 s Time delay for
temperature alarm
tTempLockOut 0.000 - 60.000 0.001 0.000 s Time delay for temperture
lockout
tResetLevelAlm 0.000 - 60.000 0.001 0.000 s Reset time delay for level
alarm
tResetLevelLO 0.000 - 60.000 0.001 0.000 s Reset time delay for level
lockout
tResetTempLO 0.000 - 60.000 0.001 0.000 s Reset time delay for
temperture lockout
tResetTempAlm 0.000 - 60.000 0.001 0.000 s Reset time delay for
temperture alarm
1MRK 505 277-UUS C Section 12
Monitoring