Functionality
The pulse function can be used, for example for pulse extensions or limiting of
operation of outputs. The PULSETIMER has a settable length.
Function block
PULSETIMER
INPUT OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 83: PULSETIMER function block
Signals
Table 143: PULSETIMER Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Table 144: PULSETIMER Output signals
Name
Type Description
OUT BOOLEAN Output signal
Settings
Table 145: PULSETIMER Non group settings (basic)
Name
Values (Range) Unit Step Default Description
t 0.000 - 90000.000 s 0.001 0.010 Pulse time length
11.3.1.5 Controllable gate function block GATE
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Controllable gate function block GATE - -
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
1MRK 505 277-UUS C Section 11
Logic
197
Technical Manual