16.2 Inputs
16.2.1 Measuring inputs
Table 360: Analog input modules
Terminal TRM
6I + 4U
TRM
8I + 2U
TRM
4I + 1I + 5U
TRM
4I + 6U
AIM
6I + 4U
AIM
4I + 1I + 5U
X101-1, 2 1/5A 1/5A 1/5A 1/5A 1/5A 1/5A
X101-3, 4 1/5A 1/5A 1/5A 1/5A 1/5A 1/5A
X101-5, 6 1/5A 1/5A 1/5A 1/5A 1/5A 1/5A
X101-7, 8 1/5A 1/5A 1/5A 1/5A 1/5A 1/5A
X101-9, 10 1/5A 1/5A 0.1/0.5A 100/220V 1/5A 0.1/0.5A
X102-1, 2 1/5A 1/5A 100/220V 100/220V 1/5A 100/220V
X102-3, 4 100/220V 1/5A 100/220V 100/220V 100/220V 100/220V
X102-5, 6 100/220V 1/5A 100/220V 100/220V 100/220V 100/220V
X102-7, 8 100/220V 100/220V 100/220V 100/220V 100/220V 100/220V
X102-9, 10 100/220V 100/220V 100/220V 100/220V 100/220V 100/220V
See the connection diagrams for information on the analog input
module variant included in a particular configured IED. The primary
and secondary rated values of the primary VT's and CT's are set for the
analog inputs of the IED.
16.2.2 Auxiliary supply voltage input
The auxiliary voltage of the IED is connected to terminals X420-1 and X420-2/3. The
terminals used depend on the power supply.
The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
Table 361: Auxiliary voltage supply of 110...250 V DC or 100...240 V AC
Case
Terminal Description
3U half 19” X420-1 - Input
X420-3 + Input
Section 16 1MRK 505 277-UUS C
IED physical connections
418
Technical Manual