10.10.4 Settings
Table 128: I103GENCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 127 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 32 - 239 - 1 32 Information number for command output
(1-255)
10.11 IED commands with position and select for IEC
60870-5-103 I103POSCMD
10.11.1 Functionality
I103POSCMD has double-point position indicators that are getting the position value
as an integer (for example from the POSITION output of the SCSWI function block)
and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE); as per standard, 0 and 3
values of the position are not supported.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type
of control)
10.11.2 Function block
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN
Figure 76: I103POSCMD function block
10.11.3 Signals
Table 129: I103POSCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of command
POSITION INTEGER 0 Position of controllable object
SELECT BOOLEAN 0 Select of controllable object
Section 10 1MRK 505 277-UUS C
Control
184
Technical Manual