Table 196: CMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3I0ZeroDb 0 - 100000 m% 1 500 Zero point clamping
3I0HiHiLim 0 - 500000 A 1 3600 High High limit (physical value)
3I0HiLim 0 - 500000 A 1 3300 High limit (physical value)
3I0LowLim 0 - 500000 A 1 0 Low limit (physical value)
3I0LowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)
I1ZeroDb 0 - 100000 m% 1 500 Zero point clamping
I1HiHiLim 0 - 500000 A 1 1200 High High limit (physical value)
I1HiLim 0 - 500000 A 1 1100 High limit (physical value)
I1LowLim 0 - 500000 A 1 0 Low limit (physical value)
I1LowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I2ZeroDb 0 - 100000 m% 1 500 Zero point clamping
I2HiHiLim 0 - 500000 A 1 1200 High High limit (physical value)
I2HiLim 0 - 500000 A 1 1100 High limit (physical value)
I2LowLim 0 - 500000 A 1 0 Low limit (physical value)
I2LowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)
12.1.5.5 Monitored data
Table 197: CMSQI Monitored data
Name
Type Values (Range) Unit Description
3I0 REAL - A 3I0 Amplitude
3I0ANGL REAL - deg 3I0 Angle
I1 REAL - A I1 Amplitude
I1ANGL REAL - deg I1 Angle
I2 REAL - A I2 Amplitude
I2ANGL REAL - deg I2Angle
1MRK 505 277-UUS C Section 12
Monitoring
231
Technical Manual

Table of Contents