EasyManua.ls Logo

ABB REB650 - Settings

ABB REB650
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 35: EF4PTOC (51N_67N) Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRST1 BOOLEAN Trip signal from step 1
TRST2 BOOLEAN Trip signal from step 2
TRST3 BOOLEAN Trip signal from step 3
TRST4 BOOLEAN Trip signal from step 4
PICKUP BOOLEAN General pickup signal
PU_ST1 BOOLEAN Pickup signal step 1
PU_ST2 BOOLEAN Pickup signal step 2
PU_ST3 BOOLEAN Pickup signal step 3
PU_ST4 BOOLEAN Pickup signal step 4
PUFW BOOLEAN Forward directional pickup signal
PUREV BOOLEAN Reverse directional pickup signal
2NDHARMD BOOLEAN 2nd harmonic block signal
7.2.5 Settings
Table 36: EF4PTOC (51N_67N) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
EnaDir Disable
Enable
- - Enable Enabling the Directional calculation
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
polMethod Voltage
Current
Dual
- - Voltage Type of polarization
VPolMin 1 - 100 %VB 1 1 Minimum voltage level for polarization (UN or
U2) in % of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization (IN or
I2) in % of IBase
RPol 0.50 - 1000.00 ohm 0.01 5.00 Real part of source Z to be used for current
polarisation
XPol 0.50 - 3000.00 ohm 0.01 40.00 Imaginary part of source Z to be used for
current polarisation
I>Dir 1 - 100 %IB 1 10 Current level (IN or I2) for direction release in
% of IBase
2ndHarmStab 5 - 100 % 1 20 Second harmonic restrain operation in % of
IN magnitude
Table continues on next page
1MRK 505 277-UUS C Section 7
Current protection
85
Technical Manual