12.19 Measurands user defined signals for IEC 60870-5-103
I103MEASUSR
12.19.1 Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each block in
the private range, and the Information number parameter for each block.
12.19.2 Function block
IEC10000288-1-en.vsd
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288 V1 EN
Figure 140: I103MEASUSR function block
12.19.3 Signals
Table 271: I103MEASUSR Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
INPUT1 REAL 0.0 Service value for measurement on input 1
INPUT2 REAL 0.0 Service value for measurement on input 2
INPUT3 REAL 0.0 Service value for measurement on input 3
INPUT4 REAL 0.0 Service value for measurement on input 4
INPUT5 REAL 0.0 Service value for measurement on input 5
INPUT6 REAL 0.0 Service value for measurement on input 6
INPUT7 REAL 0.0 Service value for measurement on input 7
INPUT8 REAL 0.0 Service value for measurement on input 8
INPUT9 REAL 0.0 Service value for measurement on input 9
1MRK 505 277-UUS C Section 12
Monitoring
335
Technical Manual

Table of Contents